Unit 4: Electromagnetic Induction
- 1. Electric Flux, Magnetic Flux, and Electromotive Force (EMF)
- 2. Faraday's Law of Induction (Integral and Differential Forms)
- 3. Lenz's Law and Conservation of Energy
- 4. Self-Inductance (L) and Mutual Inductance (M)
- 5. Self-Inductances in Series and Parallel
- 6. Self-Inductance Calculations (Solenoid, Coaxial Cylinders, Toroid)
- 7. Mutual Inductance Between Two Coaxial Solenoids
- 8. Coefficient of Coupling and Its Derivation
- 9. Energy Stored in a Magnetic Field
- 10. Transformer Principles and Energy Losses
1. Electric Flux, Magnetic Flux, and Electromotive Force (EMF)
Electric Flux (ΦE)
Electric flux measures the total number of electric field lines passing normally through a given surface area in an electric field.
Definition: The surface integral of the electric field vector E over a closed or open surface A is defined as the electric flux:
ΦE = ∫ E · dA = ∫ E cos θ dA
The SI unit of electric flux is Volt-meter (V·m) or Newton-meter2 per Coulomb (N·m2/C).
Magnetic Flux (ΦB)
Magnetic flux measures the total number of magnetic field lines passing perpendicular through a surface.
Definition: The surface integral of the magnetic field vector B over a surface area A is defined as the magnetic flux:
ΦB = ∫ B · dA = B A cos θ
where θ is the angle between the magnetic field vector B and the area vector A (which is normal to the surface).
- Maximum Flux: Occurs when the surface is perpendicular to magnetic field lines (θ = 0°, cos 0° = 1), so ΦB = B A.
- Zero Flux: Occurs when the surface is parallel to magnetic field lines (θ = 90°, cos 90° = 0), so ΦB = 0.
- SI Unit: Weber (Wb) or Tesla-meter2 (T·m2). 1 Wb = 1 T·m2.
| Property | Electric Flux (ΦE) | Magnetic Flux (ΦB) |
|---|---|---|
| Field Vector | Electric Field (E) | Magnetic Field (B) |
| Formula | ΦE = ∫ E · dA | ΦB = ∫ B · dA |
| SI Unit | V·m or N·m2/C | Weber (Wb) or T·m2 |
| Closed Surface Integral | ∯ E · dA = Qencl / ε0 (Gauss's Law for Electrostatics) | ∯ B · dA = 0 (Gauss's Law for Magnetism - no magnetic monopoles) |
Electro-motive Force (EMF)
Electromotive Force (e or ε) is the work done per unit charge by a non-electrostatic source in moving a charge around a closed conductive loop.
Mathematical Definition: e = ∲ fnc · dl = -dΦB / dt
Despite being called a 'force', EMF is not a mechanical force; it is an electric potential difference measured in Volts (V), where 1 V = 1 Joule per Coulomb (J/C).
2. Faraday's Law of Induction (Integral and Differential Forms)
Fundamental Statement
Faraday's Law of Electromagnetic Induction states that whenever there is a change in the magnetic flux linked with a closed circuit, an electromotive force (EMF) is induced in the circuit. The magnitude of the induced EMF is directly proportional to the time rate of change of magnetic flux through the circuit.
1. Integral Form of Faraday's Law
The induced EMF around a closed path boundary C enclosing a surface S is given by:
e = -dΦB / dt = -d/dt [ ∫S B · dA ]
Since the induced EMF is also defined as the line integral of the induced electric field E along the closed contour C:
∲C E · dl = -d/dt ∫S B · dA
If the contour C is stationary with respect to time, the time derivative can be brought inside the integral as a partial derivative:
∲C E · dl = -∫S (∂B / ∂t) · dA
2. Differential Form of Faraday's Law
To obtain the point or differential form, apply Stokes' Theorem to convert the line integral of the electric field into a surface integral:
∲C E · dl = ∫S (∇ × E) · dA
Substituting this relation into the integral form gives:
∫S (∇ × E) · dA = -∫S (∂B / ∂t) · dA
Rearranging the integrals over the same surface S:
∫S [ (∇ × E) + (∂B / ∂t) ] · dA = 0
Since this equality holds for any arbitrary surface S, the integrand itself must vanish identically everywhere:
Differential Form: ∇ × E = -∂B / ∂t
Exam Observation: In electrostatics, ∇ × E = 0 (conservative electric field). In time-varying electromagnetic fields, ∇ × E ≠ 0, showing that induced electric fields are non-conservative and form closed loops.
3. Lenz's Law and Conservation of Energy
Lenz's Law Statement
Lenz's Law: The direction of the induced current (or induced EMF) is always such that it produces a magnetic field that opposes the change in magnetic flux that produced it.
This law accounts for the negative sign in Faraday's equation: e = -dΦB / dt.
Proof of Conservation of Energy
Lenz's law is a direct consequence of the Principle of Conservation of Energy:
- Consider a bar magnet moving towards a stationary conducting coil with its North pole facing the loop.
- As the magnet approaches, the magnetic flux through the loop increases.
- According to Lenz's law, an induced current flows in a counter-clockwise direction (when viewed from the magnet side), creating an induced North pole facing the approaching magnet.
- Like poles repel; hence, a repulsive mechanical force acts on the approaching magnet.
- To keep moving the magnet towards the coil, external mechanical work must be performed against this repulsive force.
- This mechanical work is converted directly into electrical energy, which dissipates as Joule heat (I2R) in the coil circuit.
Important Note: If the induced current were in the opposite direction (attracting the magnet), the magnet would accelerate towards the coil without external work, generating electrical energy continuously out of nothing, which violates the Law of Conservation of Energy.
4. Self-Inductance (L) and Mutual Inductance (M)
Self-Inductance (L)
Self-inductance is the property of an electric circuit by virtue of which it opposes any change in the current flowing through itself by inducing a counter-EMF.
The total magnetic flux linkage (NΦB) in a coil is directly proportional to the current (I) flowing through it:
NΦB = L I
Self-Inductance Coefficient: L = NΦB / I
Induced EMF: e = -L (dI / dt)
The SI unit of inductance is the Henry (H). One Henry is defined as the self-inductance of a circuit in which an induced EMF of 1 Volt is produced when current changes at the rate of 1 Ampere per second (1 H = 1 V·s/A).
Mutual Inductance (M)
Mutual inductance is the property of two neighboring coils by virtue of which a changing current in one coil (primary) induces an EMF in the secondary coil.
The flux linkage in coil 2 (secondary) due to current in coil 1 (primary) is:
N2 Φ21 = M I1
Mutual Inductance Coefficient: M = (N2 Φ21) / I1
Induced EMF in Secondary: e2 = -M (dI1 / dt)
By reciprocity principle: M12 = M21 = M.
5. Self-Inductances in Series and Parallel
Inductors in Series
Consider two inductors with self-inductances L1 and L2 connected in series.
Case 1: No Magnetic Linkage (M = 0)
Total EMF e = e1 + e2 = -L1 (dI/dt) - L2 (dI/dt) = -(L1 + L2) (dI/dt)
Leq = L1 + L2
Case 2: With Mutual Coupling (M ≠ 0)
- Aiding Flux (Currents in same sense): Leq = L1 + L2 + 2M
- Opposing Flux (Currents in opposite sense): Leq = L1 + L2 - 2M
Inductors in Parallel
Consider two inductors L1 and L2 connected in parallel without mutual coupling (M = 0).
Total current I = I1 + I2. Differentiating with respect to time:
dI/dt = (dI1/dt) + (dI2/dt)
Since voltage across both inductors is equal (e = -L1 dI1/dt = -L2 dI2/dt = -Leq dI/dt):
(e / Leq) = (e / L1) + (e / L2)
1 / Leq = (1 / L1) + (1 / L2) → Leq = (L1 L2) / (L1 + L2)
| Configuration | Without Coupling (M = 0) | With Coupling (M ≠ 0) |
|---|---|---|
| Series Connection | Leq = L1 + L2 | Leq = L1 + L2 ± 2M |
| Parallel Connection | Leq = (L1 L2) / (L1 + L2) | Leq = (L1 L2 - M2) / (L1 + L2 ∓ 2M) |
6. Self-Inductance Calculations (Solenoid, Coaxial Cylinders, Toroid)
1. Long Solenoid
Consider a long solenoid of length l, cross-sectional area A, total turns N, and turn density n = N / l.
- Magnetic field inside long solenoid: B = μ0 n I = μ0 (N / l) I
- Flux through a single turn: Φ1 = B A = (μ0 N I A) / l
- Total flux linkage for N turns: Φtotal = N Φ1 = (μ0 N2 A I) / l
- Using L = Φtotal / I:
L = (μ0 N2 A) / l = μ0 n2 A l
If filled with a magnetic core of relative permeability μr, then L = (μ0 μr N2 A) / l.
2. Coaxial Cylinders
Consider two coaxial thin cylindrical shells of length l with inner radius a and outer radius b carrying equal and opposite current I.
- Magnetic field in the region between cylinders (a < r < b) using Ampere's Law: B=(μ0 I) / (2π r)
- Consider a strip of width dr and length l between the cylinders. The area element dA = l dr.
- Flux through this strip: dΦ = B dA = [ (μ0 I) / (2π r) ] l dr
- Integrating from r = a to r = b:
Φ = ∫ab [ (μ0 I l) / (2π) ] (dr / r) = [ (μ0 I l) / (2π) ] ln(b / a) - Since L = Φ / I:
L = [ (μ0 l) / (2π) ] ln(b / a)
3. Toroid
Consider a toroid of N turns having inner radius r1, outer radius r2, and rectangular cross-section of height h.
- Magnetic field at radius r inside core: B = (μ0 N I) / (2π r)
- Flux through an elemental strip of width dr and height h: dΦ = B (h dr) = [ (μ0 N I h) / (2π) ] (dr / r)
- Integrating from r1 to r2:
Φ1 = [ (μ0 N I h) / (2π) ] ln(r2 / r1) - Total flux linkage Φtotal = N Φ1 = [ (μ0 N2 I h) / (2π) ] ln(r2 / r1)
- Dividing by I gives self-inductance:
Rectangular Cross-section: L = [ (μ0 N2 h) / (2π) ] ln(r2 / r1)
Circular Cross-section (mean radius ravg, area A): L ≈ (μ0 N2 A) / (2π ravg)
7. Mutual Inductance Between Two Coaxial Solenoids
Consider two thin, closely wound coaxial solenoids of length l. Inner solenoid S1 has radius r1, number of turns N1. Outer solenoid S2 has radius r2 (r2 > r1), number of turns N2.
Derivation Steps:
- Pass current I1 through inner solenoid S1.
- The uniform magnetic field generated inside S1 is:
B1 = μ0 (N1 / l) I1 - Since r1 < r2, the magnetic field B1 exists only inside S1 (area A1 = π r12) and is zero outside S1.
- Flux through a single turn of outer solenoid S2 due to B1 is:
Φ21(single) = B1 A1 = [ μ0 (N1 / l) I1 ] (π r12) - Total magnetic flux linkage with all N2 turns of solenoid S2:
Φ21 = N2 Φ21(single) = (μ0 N1 N2 π r12 I1) / l - By definition, mutual inductance M21 = Φ21 / I1:
M = (μ0 N1 N2 A1) / l
where A1 = π r12 is the cross-sectional area of the inner solenoid.
8. Coefficient of Coupling and Its Derivation
Definition
The coefficient of coupling (k) is a measure of the degree of magnetic linkage between two coils. It represents the fraction of magnetic flux produced by one coil that passes through another coil.
k = M / √(L1 L2) (0 ≤ k ≤ 1)
- Tight Coupling (k = 1): 100% flux produced by coil 1 links with coil 2.
- Loose Coupling (0 < k < 1): Partial flux linkage.
- Zero Coupling (k = 0): No flux linkage (coils perpendicular or isolated).
Derivation
Consider two solenoids S1 and S2 of length l and cross-sectional area A wound over each other.
Self-inductance of coil 1: L1 = (μ0 N12 A) / l
Self-inductance of coil 2: L2 = (μ0 N22 A) / l
Multiplying L1 and L2:
L1 L2 = [ (μ0 N12 A) / l ] × [ (μ0 N22 A) / l ] = [ (μ0 N1 N2 A) / l ]2
Taking the square root on both sides:
√(L1 L2) = (μ0 N1 N2 A) / l
Notice that the right-hand side is equal to the ideal mutual inductance Mmax when all flux links both coils:
Mmax = √(L1 L2)
If only a fraction k of magnetic flux links coil 2, then actual mutual inductance is M = k Mmax = k √(L1 L2).
Derived Formula: k = M / √(L1 L2)
9. Energy Stored in a Magnetic Field
Derivation of Stored Energy in an Inductor
When an increasing current flows through an inductor, an opposing back EMF e = -L (dI/dt) is produced. To maintain current flow, external energy must be supplied against this back EMF.
- Work done in small time dt: dW = P dt = e I dt = (L dI / dt) I dt = L I dI
- Total work done to establish current from 0 to steady value I:
U = ∫ dW = ∫0I L I dI = (1/2) L I2
Energy Stored in Inductor: U = (1/2) L I2
Magnetic Energy Density (uB)
Energy density is defined as the magnetic energy stored per unit volume inside the magnetic field region.
For a long solenoid of length l and area A:
- Inductance L = (μ0 N2 A) / l
- Magnetic field B = (μ0 N I) / l → I = (B l) / (μ0 N)
- Substitute L and I into energy equation:
U = (1/2) [ (μ0 N2 A) / l ] [ (B l) / (μ0 N) ]2 = (1/2) [ (μ0 N2 A) / l ] [ (B2 l2) / (μ02 N2) ] = (B2 A l) / (2 μ0) - Since volume V = A l:
uB = U / V = [ (B2 A l) / (2 μ0) ] / (A l)
Magnetic Energy Density: uB = B2 / (2 μ0)
10. Transformer Principles and Energy Losses
Operating Principle
A transformer is a static electrical device that transfers electrical energy between two or more circuits through mutual induction, changing AC voltage levels while preserving frequency.
Transformation Ratio Equation:
Vs / Vp = Ns / Np = Ip / Is = K
- Step-up Transformer: Ns > Np → Vs > Vp and Is < Ip
- Step-down Transformer: Ns < Np → Vs < Vp and Is > Ip
Detailed Losses in Transformers
| Loss Type | Physical Cause | Minimization Technique |
|---|---|---|
| 1. Copper Loss (I2R Loss) | Joule heat generation in primary and secondary winding resistances. | Use thick copper wires with low resistance for high current windings. |
| 2. Eddy Current Loss | Time-varying magnetic flux induces circulating loop currents inside the solid iron core, producing heat. | Use a laminated iron core insulated with varnish instead of a solid core. |
| 3. Hysteresis Loss | Energy spent continuously magnetizing and demagnetizing the iron core during each AC cycle. | Use core material with narrow hysteresis loop area, such as Silicon Steel. |
| 4. Flux Leakage Loss | Not all magnetic flux produced by primary coil links with secondary coil due to air gap leakage. | Shell-type core construction or winding primary and secondary coils over each other. |
| 5. Magnetostriction / Humming Loss | Periodic contraction and expansion of core under magnetic field producing sound vibration. | Tight mechanical clamping of core laminations and high-grade core materials. |